BQSR Series Spring Return Electric Actuator

Standard Specifications
| Power Supply: | 24 VDC(BQSR-068 only) 120/220VAC 1PH,50/60 Hz | |
| Motor | 24VDC | 24V 100W 5A(BQSR-068 only) |
| 110VAC | 110V, 50/60Hz, 30W, 0.5A | |
| 220VAC | 220V,50/60Hz, 30W,0.33A | |
| Limit Switches | 24VDC | 15A 1/2HP @125/250VAC(BQSR-068 only) |
| 11OVAC | 11A 1/3HP @125/250/277VAC 1/2A 125VAC, 1 1/4A 250VAC | |
| 220VAC | 11A 1/3HP @125/250/277VAC 1/2A 125VAC, 11/4A 250VAC | |
| Stall Protection: | Built in thermal protection,Open at 130±5°C,Close at 85±15°C | |
| Travel Angle: | 0 to 90°±10° | |
| Indicator: | Continuous position indicator | |
| Space Heater: | 10W 2.5A Anti-Condensation | |
| Cable Conduit: | Two 3/4" NPT (BQSR-034 has One 3/4" NPT) | |
| Lubrication: | Grease Synthetic | |
| Terminal Block: | Spring loaded lever push type | |
| Materials: | Carbon Steel, Alloy Steel, Spring Steel,Stainless Steel, Aluminum Alloy, NBR,ABS and Polycarbonate Plastic | |
| Ambient Temperature: | -40°F to 140°F(-40°C to 60°C) | |
| Bxternal Coating: | Powder Coating | |
Technical and Dimensional Infomation
Dimensions(mm)
| Model | IS05211 | A1 | A2 | B1 | B2 | C1 | C2 | D | AND | F | G | H | I | J |
| BQSR034 | F07 | 5/16-18 | - | 12 | - | 70 | - | 17 | 29 | 96 | 195 | 97.5 | 202.4 | 105 |
| BQSR068 | FO7/F10 | 5/16-18 | 3/8-16 | 15 | 15 | 70 | 102 | 19 | 48 | - | 246 | 123 | 245 | 123 |
| BQSR136 | F07/F10 | 5/16-18 | 3/8-16 | 12 | 15 | 70 | 102 | 22 | 31 | 135.6 | 286 | 143 | 286 | 143 |
| BQSR204 | F07/F10 | 5/16-18 | 3/8-16 | 12 | 15 | 70 | 102 | 22 | 31 | 135.6 | 286 | 143 | 286 | 143 |
| BQSR360 | F10/F12 | 3/8-16 | 1/2-13 | 18.8 | 22.6 | 102 | 105 | 27 | 43.7 | 155.7 | 357 | 178.6 | 357 | 178.6 |
| Model | K | L | M | N | THE | P | Q | R | S | T | IN | In | IN | X |
| BQSR034 | 7 | 195 | 383 | 35 | 85 | 195 | - | 148.6 | 22 | - | - | 34 | 21 | 25.4 |
| BQSR068 | 5 | 322 | 572 | 105 | 100 | 298.5 | 40 | 136.4 | 72 | - | 70 | - | 10 | 50.8 |
| BQSR136 | 2 | 309 | 559 | 30 | 126 | 309 | 40 | 138 | 72 | - | - | - | - | 50.8 |
| BQSR204 | 2 | 309 | 721 | 30 | 126 | 443.5 | 40 | 139 | 72 | 162 | - | - | - | 50.8 |
| BQSR360 | 2 | 466 | 766 | 40 | 160 | 436 | 50 | 180 | 72 | - | - | - | - | 50.8 |
Bqsr With 2rdgo

Wiring Diagram Reference
| Model | Description | Drawing |
| BQSR034thru BQSR360 | 115/220 VAC 1PH, Two Position | SE01668 |
| BQSR068 | 24 VDC | SE01669 |
Technical Data
| Actuator Model | Spring EndTorque | 90Cycle Time | SpringFail Time | Motor Size | Rated Amps | Duty Cycle | Weight | |||
| DC | AC | Standard | w/Manua Override | |||||||
| SIZE | N-m | seconds | seconds | Watts | 24V | 110V | 220V | % | KGs. | KGs. |
| BQSR034 | 34 | 10 | 4 | 30 | N/A | 1 | 0.5 | 50 | 14.4 | 32.4 |
| BQSR068 | 68 | 30 | 2 | 30 | 2 | 1 | 0.5 | 50 | 27.9 | 45.9 |
| BQSR136 | 136 | 30 | 7 | 30 | N/A | 1 | 0.5 | 50 | 36 | 54 |
| BQSR204 | 204 | 30 | 7 | 30 | N/A | 1 | 0.5 | 50 | 54 | 72 |
| BQSR360 | 360 | 30 | 4 | 80 | 5 | 1.4 | 0.7 | 50 | 96.8 | 126.5 |

BE01669
| LIMIT SWITCH OPERATION | |||
| SWITCH | CLOSE←INTERMEDIATE→OPEN | ||
| CLS 1-2 | ---- | ---- | |
| CLS 1-3 | ---- | ||
| OLS 1-2 | ---- | ---- | ---- |
| OLS 1-3 | ---- | ||
| ACLS 1-2 | ---- | ---- | |
| ACLS 1-3 | ---- | ||
| AOLS 1-2 | ---- | ---- | |
| AOLS 1-3 | ---- | ||
| SYMBOL | DESCRIPTION | RATING | |
| ACLS | AUX.CLOSE LIMIT SWITCH (TOP) | 250VAC 15A | |
| CLS | CLOSE LIMIT SWITCH | 250VAC 15A | |
| AOLS | AUX.OPEN LIMIT SWITCH | 250VAC 15A | |
| OLS | OPEN LIMIT SWITCH (BOT) | 250VAC 15A | |
| *EACH ACTUATOR SHOULD BE POWERED THROUGH IT'S OWN INDIVIDAL SWITCH OR RELAY CONTACTS TO PREVENT CROS SFEED BETWEEN TWO OR MORE ACTUATORS. | |||
Operation Notes:
1.Power to terminal 2 & 4 will drive motor CCW.Brake energizes when NO of OLS closes to hold actuator in CCW position.
2.Power to terminal 2 & 6 will drive motor CW.Brake energizes when NO of CLS closes to hold actuator in CW position.
3.Power to terminal 2 & 5 will energize brake and hold actuator in intermediate STOP position.
4.Loss of power will release spring clutch and return actuator to fail position (limited by adjustable stop).
BE01668
| LIMIT SWITCH OPERATION | |||
| SWITCH | CLOSE←INTERMEDIATE→OPEN | ||
| CLS 1-2 | ---- | ---- | |
| CLS 1-3 | ---- | ||
| OLS 1-2 | ---- | ---- | ---- |
| OLS 1-3 | ---- | ||
| ACLS 1-2 | ---- | ---- | |
| ACLS 1-3 | ---- | ||
| AOLS 1-2 | ---- | ---- | |
| AOLS 1-3 | ---- | ||
| SYMBOL | DESCRIPTION | RATING | |
| ACLS | AUX.CLOSE LIMIT SWITCH (TOP) | 250VAC 15A | |
| CLS | CLOSE LIMIT SWITCH | 250VAC 15A | |
| AOLS | AUX.OPEN LIMIT SWITCH | 250VAC 15A | |
| OLS | OPEN LIMIT SWITCH (BOT) | 250VAC 15A | |
| *EACH ACTUATOR SHOULD BE POWERED THROUGH IT'S OWN INDIVIDAL SWITCH OR RELAY CONTACTS TO PREVENT CROS SFEED BETWEEN TWO OR MORE ACTUATORS. | |||
Operation Notes:
1.Power to terminal 2 & 4 will drive motor CCW.Brake energizes when NO of OLS closes to hold actuator in CCW position.
2.Power to terminal 2 & 6 will drive motor CW.Brake energizes when NO of CLS closes to hold actuator in CW position.
3.Power to terminal 2 & 5 will energize brake and hold actuator in intermediate STOP position.
4.Loss of supply power will release brake and return actuator to fail position (limited by odjustable stop).