BQSR Series Spring Return Electric Actuator - Reliable China Suppliers and Factory for Efficient Control Solutions
Standard Specifications
| Power Supply: | 24 VDC(BQSR-068 only) 120/220VAC 1PH,50/60 Hz | |
| Motor | 24VDC | 24V 100W 5A(BQSR-068 only) |
| 110VAC | 110V, 50/60Hz, 30W, 0.5A | |
| 220VAC | 220V,50/60Hz, 30W,0.33A | |
| Limit Switches | 24VDC | 15A 1/2HP @125/250VAC(BQSR-068 only) |
| 11OVAC | 11A 1/3HP @125/250/277VAC 1/2A 125VAC, 1 1/4A 250VAC | |
| 220VAC | 11A 1/3HP @125/250/277VAC 1/2A 125VAC, 11/4A 250VAC | |
| Stall Protection: | Built in thermal protection,Open at 130±5°C,Close at 85±15°C | |
| Travel Angle: | 0 to 90° ± 10° | |
| Indicator: | Continuous position indicator | |
| Space Heater: | 10W 2.5A Anti-Condensation | |
| Cable Conduit: | Two 3/4" NPT (BQSR-034 has One 3/4" NPT) | |
| Lubrication: | Grease Synthetic | |
| Terminal Block: | Spring loaded lever push type | |
| Materials: | Carbon Steel, Alloy Steel, Spring Steel,Stainless Steel, Aluminum Alloy, NBR,ABS and Polycarbonate Plastic | |
| Ambient Temperature: | -40°F to 140°F(-40°C to 60°C) | |
| External Coating: | Powder Coating | |
Technical and Dimensional Information
Dimensions(mm)
| Model | ISO5211 | A1 | A2 | B1 | B2 | C1 | C2 | D | AND | F | G | H | I | J |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| BQSR034 | F07 | 5/16-18 | - | 12 | - | 70 | - | 17 | 29 | 96 | 195 | 97.5 | 202.4 | 105 |
| BQSR068 | F07/F10 | 5/16-18 | 3/8-16 | 15 | 15 | 70 | 102 | 19 | 48 | - | 246 | 123 | 245 | 123 |
| BQSR136 | F07/F10 | 5/16-18 | 3/8-16 | 12 | 15 | 70 | 102 | 22 | 31 | 135.6 | 286 | 143 | 286 | 143 |
| BQSR204 | F07/F10 | 5/16-18 | 3/8-16 | 12 | 15 | 70 | 102 | 22 | 31 | 135.6 | 286 | 143 | 286 | 143 |
| BQSR360 | F10/F12 | 3/8-16 | 1/2-13 | 18.8 | 22.6 | 102 | 105 | 27 | 43.7 | 155.7 | 357 | 178.6 | 357 | 178.6 |
| Model | K | L | M | N | THE | P | Q | R | S | T | IN | In | IN | X |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| BQSR034 | 7 | 195 | 383 | 35 | 85 | 195 | - | 148.6 | 22 | - | - | 34 | 21 | 25.4 |
| BQSR068 | 5 | 322 | 572 | 105 | 100 | 298.5 | 40 | 136.4 | 72 | - | 70 | - | 10 | 50.8 |
| BQSR136 | 2 | 309 | 559 | 30 | 126 | 309 | 40 | 138 | 72 | - | - | - | - | 50.8 |
| BQSR204 | 2 | 309 | 721 | 30 | 126 | 443.5 | 40 | 139 | 72 | 162 | - | - | - | 50.8 |
| BQSR360 | 2 | 466 | 766 | 40 | 160 | 436 | 50 | 180 | 72 | - | - | - | - | 50.8 |
Bqsr With 2rdgo
Wiring Diagram Reference
| Model | Description | Drawing |
|---|---|---|
| BQSR034 thru BQSR360 | 115/220 VAC 1PH, Two Position | SE01668 |
| BQSR068 | 24 VDC | SE01669 |
Technical Data
| Actuator Model | Spring End Torque (N-m) | 90 Cycle Time (seconds) | Spring Fail Time (seconds) | Motor Size (Watts) | Rated Amps | Duty Cycle (%) | Weight (KGs) | |||
|---|---|---|---|---|---|---|---|---|---|---|
| DC 24V | AC 110V | AC 220V | Standard | w/ Manual Override | ||||||
| BQSR034 | 34 | 10 | 4 | 30 | N/A | 1 | 0.5 | 50 | 14.4 | 32.4 |
| BQSR068 | 68 | 30 | 2 | 30 | 2 | 1 | 0.5 | 50 | 27.9 | 45.9 |
| BQSR136 | 136 | 30 | 7 | 30 | N/A | 1 | 0.5 | 50 | 36 | 54 |
| BQSR204 | 204 | 30 | 7 | 30 | N/A | 1 | 0.5 | 50 | 54 | 72 |
| BQSR360 | 360 | 30 | 4 | 80 | 5 | 1.4 | 0.7 | 50 | 96.8 | 126.5 |
BE01669
Limit Switch Operation
| SWITCH | CLOSE ← INTERMEDIATE → OPEN | ||
|---|---|---|---|
| CLS 1-2 | ---- | ---- | |
| CLS 1-3 | ---- | ||
| OLS 1-2 | ---- | ---- | ---- |
| OLS 1-3 | ---- | ||
| ACLS 1-2 | ---- | ---- | |
| ACLS 1-3 | ---- | ||
| AOLS 1-2 | ---- | ---- | |
| AOLS 1-3 | ---- | ||
| SYMBOL | DESCRIPTION | RATING | |
|---|---|---|---|
| ACLS | AUX.CLOSE LIMIT SWITCH (TOP) | 250VAC 15A | |
| CLS | CLOSE LIMIT SWITCH | 250VAC 15A | |
| AOLS | AUX.OPEN LIMIT SWITCH | 250VAC 15A | |
| OLS | OPEN LIMIT SWITCH (BOT) | 250VAC 15A | |
| *EACH ACTUATOR SHOULD BE POWERED THROUGH IT'S OWN INDIVIDAL SWITCH OR RELAY CONTACTS TO PREVENT CROS SFEED BETWEEN TWO OR MORE ACTUATORS. | |||
Operation Notes:
- 1.Power to terminal 2 & 4 will drive motor CCW.Brake energizes when NO of OLS closes to hold actuator in CCW position.
- 2.Power to terminal 2 & 6 will drive motor CW.Brake energizes when NO of CLS closes to hold actuator in CW position.
- 3.Power to terminal 2 & 5 will energize brake and hold actuator in intermediate STOP position.
- 4.Loss of power will release spring clutch and return actuator to fail position (limited by adjustable stop).
BE01668
| SWITCH | CLOSE ← INTERMEDIATE → OPEN | ||
|---|---|---|---|
| CLS 1-2 | ---- | ---- | |
| CLS 1-3 | ---- | ||
| OLS 1-2 | ---- | ---- | ---- |
| OLS 1-3 | ---- | ||
| ACLS 1-2 | ---- | ---- | |
| ACLS 1-3 | ---- | ||
| AOLS 1-2 | ---- | ---- | |
| AOLS 1-3 | ---- | ||
| SYMBOL | DESCRIPTION | RATING | |
|---|---|---|---|
| ACLS | AUX.CLOSE LIMIT SWITCH (TOP) | 250VAC 15A | |
| CLS | CLOSE LIMIT SWITCH | 250VAC 15A | |
| AOLS | AUX.OPEN LIMIT SWITCH | 250VAC 15A | |
| OLS | OPEN LIMIT SWITCH (BOT) | 250VAC 15A | |
| *EACH ACTUATOR SHOULD BE POWERED THROUGH IT'S OWN INDIVIDAL SWITCH OR RELAY CONTACTS TO PREVENT CROS SFEED BETWEEN TWO OR MORE ACTUATORS. | |||
Operation Notes:
- 1.Power to terminal 2 & 4 will drive motor CCW.Brake energizes when NO of OLS closes to hold actuator in CCW position.
- 2.Power to terminal 2 & 6 will drive motor CW.Brake energizes when NO of CLS closes to hold actuator in CW position.
- 3.Power to terminal 2 & 5 will energize brake and hold actuator in intermediate STOP position.
- 4.Loss of supply power will release brake and return actuator to fail position (limited by odjustable stop).
Frequently Asked Questions
Q1: What power supply options are available for the BQSR series actuators?
The BQSR-068 model supports 24 VDC, while other models in the series operate on 120/220VAC 1PH, 50/60 Hz.
Q2: What is the operating temperature range for these spring return actuators?
The BQSR series is designed to operate in ambient temperatures ranging from -40°F to 140°F (-40°C to 60°C).
Q3: How does the stall protection system safeguard the motor?
The actuators feature built-in thermal protection. The circuit opens at 130±5°C to prevent overheating and automatically closes once it cools down to 85±15°C.
Q4: What materials are used in the construction of the BQSR actuators?
The construction utilizes high-quality materials including Carbon Steel, Alloy Steel, Spring Steel, Stainless Steel, Aluminum Alloy, NBR, ABS, and Polycarbonate Plastic, finished with a protective Powder Coating.
Q5: Why is it recommended to power each actuator through its own individual switch or relay?
Each actuator must be powered through its own individual switch or relay contacts to prevent cross-feed electrical interference between two or more actuators.
Q6: What is the travel angle and duty cycle of the BQSR series?
The travel angle is 0 to 90° ± 10°, and the series maintains a standard duty cycle of 50%.